Product
Specifications |
Volt |
Model |
Measurement
Range |
Resolution |
Accuracy |
Vrms (AC + DC) |
1
V to 1000 V phase to neutral |
0.1
V |
±0.5%
of nominal voltage4 |
Vpk |
1
Vpk to 1400 Vpk |
1
V |
5%
of nominal voltage |
Voltage Crest Factor (CF) |
1.0
> 2.8 |
0.01 |
±5% |
Vrms½ |
1
V to 1000 V phase to neutral |
0.1
V |
±1%
of nominal voltage |
Vfund |
1
V to 1000 V phase to neutral |
0.1
V |
±0.5%
of nominal voltage |
Amps
(accuracy excluding clamp accuracy) |
Amps
(AC + DC) |
i430-Flex
1x |
5
A to 6000 A |
1:00
AM |
±0.5%
±5 counts |
i430-Flex
10x |
0.5
A to 600 A |
0.1
A |
±0.5%
±5 counts |
1
mV/A 1x |
5
A to 2000 A |
1:00
AM |
±0.5%
±5 counts |
1
mV/A 10x |
0.5
A A to 200 A (AC only) |
0.1
A |
±0.5%
±5 counts |
Apk |
i430-Flex |
8400
Apk |
1
Arms |
±5% |
1
mV/A |
5500
Apk |
1
Arms |
±5% |
A Crest Factor (CF) |
1
to 10 |
0.01 |
±5% |
Amps½ |
i430-Flex
1x |
5
A to 6000 A |
1:00
AM |
±1%
±10 counts |
i430-Flex
10x |
0.5
A to 600 A |
0.1
A |
±1%
±10 counts |
1
mV/A 1x |
5
A to 2000 A |
1:00
AM |
±1%
±10 counts |
1
mV/A 10x |
0.5
A A to 200 A (AC only) |
0.1
A |
±1%
±10 counts |
Afund |
i430-Flex
1x |
5
A to 6000 A |
1:00
AM |
±0.5%
±5 counts |
i430-Flex
10x |
0.5
A to 600 A |
0.1
A |
±0.5%
±5 counts |
1
mV/A 1x |
5
A to 2000 A |
1:00
AM |
±0.5%
±5 counts |
1
mV/A 10x |
0.5
A A to 200 A (AC only) |
0.1
A |
±0.5%
±5 counts |
Hz |
Fluke 434 @ 50 Hz nominal |
42.50
Hz to 57.50 Hz |
0.01
Hz |
±0.01
Hz |
Fluke 434 @ 60 Hz nominal |
51.00
Hz to 69.00 Hz |
0.01
Hz |
±0.01
Hz |
Power |
Watts
(VA, var) |
i430-Flex |
max
6000 MW |
0.1
W to 1 MW |
±1%
±10 counts |
1
mV/A |
max
2000 MW |
0.1
W to 1 MW |
±1%
±10 counts |
Power Factor (Cos j/DPF) |
0
to 1 |
0.001 |
±0.1%
@ nominal load conditions |
Energy |
kWh (kVAh, kvarh) |
i430-Flex
10x |
Depends
on clamp scaling and V nominal |
±1%
±10 counts |
Energy Loss |
i430-Flex
10x |
Depends
on clamp scaling and V nominal |
±1%
±10 counts Excluding line resistance accuracy |
Harmonics |
Harmonic Order (n) |
DC, 1 to 50 Grouping: Harmonic groups
according to IEC 61000-4-7 |
Inter-Harmonic Order (n) |
OFF, 1 to 50 Grouping: Harmonic and
Interharmonic subgroups according to IEC 61000-4-7 |
Volts
% |
f |
0.0%
to 100% |
0.10% |
±0.1%
±n x 0.1% |
r |
0.0%
to 100% |
0.10% |
±0.1%
±n x 0.4% |
Absolute |
0.0
to 1000 V |
0.1
V |
±5%1 |
THD |
0.0%
to 100% |
0.10% |
±2.5% |
Amps
% |
f |
0.0%
to 100% |
0.10% |
±0.1%
±n x 0.1% |
r |
0.0%
to 100% |
0.10% |
±0.1%
±n x 0.4% |
Absolute |
0.0
to 600 A |
0.1
A |
±5%
±5 counts |
THD |
0.0%
to 100% |
0.10% |
±2.5% |
Watts
% |
f
or r |
0.0%
to 100% |
0.10% |
±n
x 2% |
Absolute |
Depends
on clamp scaling and V nominal |
— |
±5%
±n x 2% ±10 counts |
THD |
0.0%
to 100% |
0.10% |
±5% |
Phase Angle |
-360°
to +0° |
1° |
±n
x 1° |
Flicker |
Plt, Pst, Pst (1 min) Pinst |
0.00
to 20.00 |
0.01 |
±5% |
Unbalance |
Volts % |
0.0%
to 20.0% |
0.10% |
±0.1% |
Amps % |
0.0%
to 20.0% |
0.10% |
±1% |
Mains
Signaling |
Threshold Levels |
Threshold,
limits and signaling duration is programable for two signaling frequencies |
— |
— |
Signaling Frequency |
60
Hz to 3000 Hz |
0.1
Hz |
|
Relative V % |
0%
to 100% |
0.10% |
±0.4% |
Absolute V3s (3 second avg.) |
0.0
V to 1000 V |
0.1
V |
±5%
of nominal voltage |
General
Specifications |
Case |
Design Rugged, shock proof with
integrated protective holster Drip and dust proof IP51 according to IEC60529
when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3
g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 |
Display |
Brightness: 200 cd/m 2 typ. using power
adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0
in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness:
user-adjustable, temperature compensated |
Memory |
8 GB SD card (SDHC compliant, FAT32
formatted) standard, upto 32GB optionally Screen save and multiple data
memories for storing data including recordings (dependent on memory size) |
Real-Time Clock |
Time and date stamp for Trend mode,
Transient display, System Monitor and event capture |
Environmental |
Operating Temperature |
0°C ~ +40°C; +40°C ~ +50°C excl. battery |
Storage Temperature |
-20°C ~ +60°C |
Humidity |
+10°C ~ +30°C: 95% RH
non-condensing |
+30°C ~ +40°C: 75% RH
non-condensing |
+40°C ~ +50°C: 45% RH
non-condensing |
Maximum
Operating Altitude |
Up to 2,000 m (6666 ft) for CAT IV 600 V,
CAT III 1000 V |
Up to 3,000 m (10,000 ft) for CAT
III 600 V, CAT II 1000 V |
Maximum storage altitude 12 km
(40,000 ft) |
Electro-Magnetic-Compatibility (EMC) |
EN 61326 (2005-12) for emission and
immunity |
Interfaces |
Mini-USB-B, Isolated USB port for PC
connectivity SD card slot accessible behind instrument battery |